For cooling towers and evaporative condensers in an office building new construction project, sustainability consultant is aiming to get two points under the WE Credit Cooling Tower Water Use. He will perform testing for concentrations found in in condenser water. Which of following is required to be tested?
-
A
TSS
-
B
Turbidity
-
C
Total alkalinity
-
D
glyphosate
Reveal correct answer
Correct answer: C
Explanation
Total alkalinity is required to not exceed 1000 ppm. Reference: LEED BD+C Reference guide - page: 305Discussion